Duct Visionductvision.com Get in touch

Duct takeoffs + 3D shop drawings. Built around your shop.

Tell us about the job. We set up a call, go over the drawings and your shop standards, and agree on scope and timing before any work starts.

TakeoffsShop drawings3D modelsExpedited jobs welcome
Start a conversationNo files yet
What do you need?
What do you have for this job? (check all)

We'll email you to set up a call. Drawings come after we talk.

1. Tell us about the jobA few details, no files
2. Quick callScope, your standards, timing
3. We build itTraced, modeled, checked, reviewed by a person
What you get back

Real output from a real job

3D model of a retail store with all duct runs, air handlers and diffuser drops at real heights
3D model at real heightsWhole job, tight to structure
Duct shop drawing plan with numbered piece marks, joints, sizes and bottom-of-duct elevations
Numbered shop drawingPiece marks, sizes, BOD, joints
TakeoffSample
Sheet metal 22 + 24 ga891 lb
Straight duct141 LF
Liner / wrap281 / 438 sf
Fittings49
Shop pieces27
Flex34 LF
QA 11 PASS6 questions
Takeoff by gaugeInto Excel or your estimating software
Air handlers with mixing boxes, outside air tee, return and supply transitions with TDC joints
Equipment connectionsTransitions, mixing boxes, OA, return
Radius-throat bullhead tee splitting a main two ways
Every fitting detailedRadius-throat bullhead tee
Spin-in tap between two joints with elbow and flex drop to a diffuser
No taps on a seamPieces cut so branches land in clean metal
Branch with bought round elbow and flex drop to a ceiling diffuser
Drops to the ceilingBought 90, flex 5 ft max

Swipe for more →

Before we start

What a job needs

Good output starts with a complete set. Here's what we ask for once we've talked.

M
Full mechanical setPlans, schedules, details and general notes. The details and notes decide how the duct gets built.
A
Full architectural setPlans, reflected ceiling plans, sections and elevations. Ceiling heights and structure live here.
S
SpecificationsDuct, insulation and liner sections at minimum.
C
Equipment cut sheetsAir handlers, VAV boxes, fans and anything duct connects to. Connection sizes come from these.
+
Your shop standardsGauges, joints, section lengths, liner, how you split and drop. Don't have them written down? We'll go over them on the call.

Missing something? Say so on the form. Gaps come back as questions, never guesses.

Details

Tap for the details

1What's in the takeoff?
  • Sheet metal weight by gauge, from the actual pieces
  • Straight duct LF by size
  • Liner and wrap square footage, read from the spec
  • Every fitting, diffuser, grille, damper and flex run counted
  • Buy-out list (bought elbows, flex, devices)
  • Delivered in Excel or formatted for ProEst, FastEST, Trimble, Accubid or whatever you bid in
2What's in the shop drawings?
  • Duct plans with sizes and bottom-of-duct elevations
  • Numbered piece marks and a piece schedule with cut lengths
  • Fittings, dampers, access doors and devices
  • Sections where space is tight
  • Your shop's standard notes
  • AutoCAD, Revit, IFC, FreeCAD or PDF
3Which shop standards do you follow?

Yours. Send them over, or we'll walk through them on the call. Anything missing gets flagged as a question, never guessed.

StandardExample
Min gauge24 ga
Gauge breaks≤30" 24 · ≤54" 22 · ≤84" 20
JointsTDC all rect
SectionsS&D 59" · TDC 56"
Liner1", clear inside
Exposed ductFull liner, no wrap
SplitsRadius-throat bullhead tee
DropsBought 90°, flex ≤ 5'-0"
4How fast?

It depends on the size of the job and how complete the set is. Smaller jobs can come back in as little as 24 hours. We agree on a firm date on the call, before anything starts. More on expedited shop drawings and expedited takeoffs.

5How is it priced?

Per job, based on the size and what you need. You get a fixed price after we've talked and seen the set, and revision rounds are agreed up front.

6Point clouds and site scanning

Have a point cloud? Mention it on the form. Routing duct through it and flagging conflicts is quoted per job.

Need a scan? On-site LiDAR scanning in the NYC area is coming soon. Mention it on the form to get on the list.

7Do you do BIM coordination?

No. You get duct models and shop drawings in AutoCAD, Revit or IFC, ready for your BIM team to drop into the federated model. No cross-trade clash coordination and no coordination meetings.

8Who does the work?

A sheet metal estimator with years in the field, the shop and the estimating office, working with AI. The AI reads, traces and models. Every job gets checked against your rules and reviewed by a person before it goes out.

9Are my drawings kept private?

Yes. Drawings are kept private and used only for your job.

10How is a duct takeoff figured?

Surface area of each run and fitting, times the gauge weight, plus seams and joints.

sqft = 2 × (W + H) / 12 × L
weight = sqft × lb/sqft for the gauge × (1 + seam allowance)

Example: 24×12, 20 ft, 24 ga = 6.0 sqft/ft × 20 = 120 sqft × 1.156 = 138.7 lb, +15% seams = 159.5 lb.

GaugeGalv. lb/sqft
260.906
241.156
221.406
201.656
182.156

Fittings are figured from their own surface area, not as extra footage. Lined duct is usually sized clear inside, so the metal grows by twice the liner. Exposed duct often gets full liner and no wrap. The spec decides.

Have a job coming up?

Tell us about it and we'll set up a call.

Get in touch